"Transformers are our CORE business"
Spectrum Industries Catalog > Shunts > Type 860 Shunts Designed to DIN Requirements  
 

Type 860 Shunts Designed to DIN Requirements


Click on a Product to view details.

Blank

Type 860 Form A - Solid End Block Shunts

(4)
Accuracy class 0.5%
Class 0.25% also available.
Overload 120% rated current continuously
5 second ratings:
1A - 500A = 10 times rated current
501A - 2000A = 5 times rated current
2001A - 15000A = 2 times rated current

Temperature coefficient: 0.002% per ºC overall
Calibrated for 23ºC with the working range of -20ºC to +60ºC

Maximum load: for maximum accuracy, load should not exceed 0.1% of the shunt current rating.

Please call with questions regarding prices and/or non-standard options
Type 860 Form B - Solid End Block Shunts

Type 860 Form B - Solid End Block Shunts

(8)
Accuracy class 0.5%
Class 0.25% also available.
Overload 120% rated current continuously
5 second ratings:
1A - 500A = 10 times rated current
501A - 2000A = 5 times rated current
2001A - 15000A = 2 times rated current

Temperature coefficient: 0.002% per ºC overall
Calibrated for 23ºC with the working range of -20ºC to +60ºC

Maximum load: for maximum accuracy, load should not exceed 0.1% of the shunt current rating.

Please call with questions regarding prices and/or non-standard options

DC Ammeter Shunt General Information ...
Blank

Type 860 Form C - Solid End Block Shunts

(10)
Accuracy class 0.5%
Class 0.25% also available.
Overload 120% rated current continuously
5 second ratings:
1A - 500A = 10 times rated current
501A - 2000A = 5 times rated current
2001A - 15000A = 2 times rated current

Temperature coefficient: 0.002% per ºC overall
Calibrated for 23ºC with the working range of -20ºC to +60ºC

Maximum load: for maximum accuracy, load should not exceed 0.1% of the shunt current rating.

Please call with questions regarding prices and/or non-standard options